OVERVIEW
XBC Series Diesel Fire Pump Unit This high-tech masterpiece seamlessly integrates cutting-edge industrial automation control, sophisticated information processing, and advanced mechanical operation technologies. Revel in its outstanding features:
- Automatic Start and Stop: Experience seamless operations with automatic start and stop capabilities, ensuring readiness at a moment's notice.
- Automatic Speed Regulation: Effortlessly adjusts speed to suit operational demands, optimizing efficiency and performance.
- Automatic Charging: Remain powered and prepared with built-in automatic charging capabilities.
- Parameter Monitoring: Vigilantly monitors and detects essential parameters to maintain optimal functionality.
- Automatic Alarming: Provides timely, automatic alarms, keeping you informed and alert.
- Automatic Inspection: Performs thorough automatic inspections to ensure everything is in top-notch order.
- Remote Control: Enjoy the convenience and flexibility of remote control operations.
APPLICATIONS
- Fire Protection Systems:
- Fire Hydrant Systems
- Sprinkler Systems
- Water Spray Cooling Systems
- Foam Systems
- Water Cannon Systems
- Hospital Fire Protection
- Emergency Fire Water Supply
- Fire Systems for Industrial and Civil Buildings
ADVANTAGES
- Multiple Startup Options: Boasts an array of startup functions including manual start, remote signal activation, automatic startup, and emergency manual direct start, ensuring versatility and reliability.
- Automatic Operation in Fire Situations: Automatically springs into action upon receiving a valid fire signal, even compensating for power failures, phase loss, or pump malfunctions. Effortlessly switches back to electric mode once systems are restored, ensuring unwavering fire protection.
- Fire Signal Feedback: Seamlessly sends fire signals back to the control room, enhancing remote monitoring and operational oversight.
- Automatic Shutdown: Efficiently shuts down with a delay post-signal disappearance, conserving resources and ensuring safety.
- Self-Charging Voltage Regulation: Automatically charges using mains electricity, guaranteeing reliable unit start-up and continuous operation.
- Comprehensive Alarm and Protection System: Features a robust system of alarms for various issues such as startup failures, overspeed, oil pressure anomalies, coolant temperature spikes, charging failures, and battery voltage irregularities, ensuring comprehensive protection and awareness.
- Visualization Display System: Stay informed with a control panel that vividly displays crucial information like oil pressure, engine speed, charging current, and voltage.
- Integrated Structure: Ingeniously crafted with a direct coupling between the diesel engine and pump on a shared steel base, this compact and efficient design promises exceptional performance with minimal vibrations and faults, facilitating easy on-site installation.
Product Parameters
TECHNICAL PARAMETER
Pump Operating Range:
- Flow Rate: 100-430 L/S: Our pump provides an impressive flow range to meet diverse firefighting needs, ensuring optimal performance and safety in any emergency.
- Head: 60-185 m: An adaptable head range that empowers strong and effective water propulsion, delivering where it's needed most in fire emergencies.
- Transported Media: Ordinary clean water and firefighting foam liquid: Versatile media compatibility ensures seamless operation whether deploying water or foam, vital for extensive fire safety strategies.
Diesel Engine Operating Range:
- Ambient Temperature: -25 to 55°C: Capable of withstanding extreme temperatures, the diesel engine is ready to perform reliably in diverse environmental conditions, from freezing cold to scorching heat.
- Relative Humidity: <85%: Designed to function efficiently even in highly humid environments, ensuring consistent performance without compromise.
- Longitudinal Inclination: <10°: Engineered to maintain stability and functionality even on slightly inclined surfaces, adding flexibility to installation locations.
- No Conductive Dust, Corrosive Gases, or Explosive Hazards: Ensure no conductive dust or gases that can damage metal insulation or create explosion risks: Guaranteeing safety by eliminating potential hazards that could compromise the pump's integrity and effectiveness.
- Altitude and Humidity Adjustments: For ambient temperatures above 20°C, relative humidity over 30%, or altitudes exceeding 1000 meters, adjust the diesel engine power according to the manufacturer's data table: Tailor the engine's power for top performance in challenging high-altitude or humid environments, ensuring adaptability and reliability.
Control Cabinet Operating Range:
- Power Voltage Fluctuation: ≤±10%: Ensure consistent and reliable power with minimal fluctuation, safeguarding the pump's operation from electrical inconsistencies.
- Ambient Temperature: -10 to +40°C (non-freezing): Designed to operate smoothly within a broad temperature range, guaranteeing year-round reliability without freezing concerns.
- Air Relative Humidity: 20% to 90% (no condensation): Perfectly suited for environments with varied humidity levels, maintaining operational integrity without the risk of condensation-related issues.
Detailed Photos

Company Profile






FAQ